Additional Features:
- Voltage: 10V
- Current: 100A
- Power: 1000W
- Over-voltage protection
- Analog programmable
- Remote sensing
- Auto-series, auto-parallel, and auto-tracking operation
- <50us load transient recovery
- Ripple and noise (20 Hz to 20 MHz): CV: 500 uV RMS, 5 mV peak-to-peak; CC: 50 mA RMS
- Load regulation: 0.01% + 200 uV, 0.02% + 2 mA
- Line regulation: 0.01% + 200 uV, 0.02% + 2 mA
The Agilent HP 6260B employs a transistor series-regulator/triac-preregulator circuit to achieve high efficiency, excellent regulation, low ripple and noise, and moderate programming speeds in a compact full-rack width package. Additional features include built-in overvoltage crowbar protection: remote error sensing: and auto-series, auto-parallel, and auto-tracking operation. The crowbar trip point adjustment and associated overvoltage indicator are conveniently located on the front panel.
Manufacturer | Agilent, HP, Keysight |
---|---|
Condition | Used |
Current | 100 A |
Voltage | 10 V |
Power | 1 kW |
005 | 50Hz AC Input |
---|---|
009 | Ten-turn Output Voltage and Current Controls |
010 | Chassis Slides |
016 | 115 Vac ±10% Single-Phase Input |
022 | Voltage and Programming Adjust |
026 | 115 Vac ±10% Single-Phase Input |
027 | 208 Vac ±10% Single-Phase Input |
028 | 230 Vac ±10% Single-Phase Input |
040 | Resistance Programming Interface (Includes Option 022) |
- Agilent HP 6206B Operating and Service Manual
- HP 6259B, 6260B, 6261B, 6268B, 6269B Operating and Service Manual